Roberts Gorden Vacuum Assisted Linear User Manual

Page 65

Advertising
background image

SECTION 14: O

PERATION

59 of 75

14.1.1 Heater Lockout Indicator by Connector

A 230 V signal is provided which enables the ROBERTS
GORDON

®

controller, BMS system, etc. to indicate the

heater that has failed. An additional wire has to be
installed from the heater lockout indicator connector to
the monitoring computer.

See Page 57, Section 13.5.

14.1.2 Heater Lockout Indicator by Volt Free
Connector

A volt free contact relay is closed which enables the
ROBERTS GORDON

®

controller, BMS system, etc. to

indicate the heater that has failed. An additional wire has
to be installed from the heater volt free connector to the
monitoring computer.

See Page 57, Section 13.5.

14.2 Testing

Establish that a satisfactory purged gas supply and an
electrical supply is available to the heater. Ensure that all
time clocks and thermostats are set to call for heat.

With the gas supply cut off at the appliance isolating cock
and the electrical supply isolated by switching off at the
local switch and removing the appliance inlet plug, open
the control chamber secured by the two screws. Loosen
the sealing screw from the pressure test point and
remove the cover cap from the governor.

Turn on the gas supply and connect appliance electrical
plug. Ensure that the timer or thermostat, if fitted, are set
to call for full gas rate. Switch on at the local switch. The
sequence as described should take place. If not, refer to
detailed fault finding sequence. When flame is
established, check the gas pressure reading and adjust if
necessary. Refer to burner data label.

Check the gas pressure at the outlet of the gas valve.

See

Page 74, Section 18.9.1 or See Page 75, Section 18.9.2
for pressure settings or refer to the data plate.

Switch off the electrical supply (shutting down the heater),
remove pressure gauge - tighten pressure test point
screw, ensuring a tight gas seal. Replace governor cover
cap. Close burner side cover.

14.3 Commissioning (Multiburner)

1. Establish that a satisfactory purged gas supply and

an electrical supply is available to the heater.

2. ENSURE that all the dampers are in the fully open

position.

3. With the gas supply off at each of the burners and

the electrical supply isolated, open the control
chamber secured by two self tapping screws.

4. Ensure that all time clocks and thermostats are set

to call for heat.

5. Switch on the electrical supply at the main isolator.

This will start the exhaust fan.

6. Balancing Cold Vacuum

Check each burner vacuum by connecting an
inclined pressure gauge to the tee on the pressure
switch inlet side in the burner. Adjust the damper so
that the vacuum is 1.9 mbar. Repeat for each burner.

7. Starting at the end burner (furthest from the exhaust

fan), with the inclined pressure gauge connected as
described above. Turn on the gas supply and con-
nect appliance electrical plug, reset the pressure
switch by removing vacuum from the inlet side of the
pressure switch waiting several seconds and recon-
necting. The start up sequence described on

Page

58, Section 14 should take place. If not, refer to
detailed fault finding sequence. When flame is
established, check the gas pressure reading and
adjust if necessary. See data label.
Check the gas pressure at the outlet of the gas
valve.

See Page 74, Section 18.9.1 or See Page 75,

Section 18.9.2 for pressure settings or refer to the
data plate.
Switch off the electrical supply (shutting down the
heater), remove pressure gauge - refit pressure test-
point screw, ensuring a tight gas seal. Replace gov-
ernor cover cap.
Repeat this procedure for each burner in the sys-
tem.
Close the control chamber and secure with two
sheet metal screws.

8. Balancing Hot Vacuum

Reconnect all the burners on the system and allow
them to reach full operating temperature (approxi-
mately 20 minutes). Return to each burner and
recheck the hot vacuum at the tee on the inlet to the
pressure switch. Readjust the damper so that the
hot vacuum of 1.5 mbar (2.0 mbar for BH40EF) is
achieved and lock the damper in position.

14.4 System Checks

Switch on again at the local switch to ensure smooth
ignition. Carry out the following system checks:
When running, turn off the gas supply at the appliance.
The heater will immediately shut down followed by three
ignition attempts followed by lockout.
Linear and Double Linear only:
When running, disconnect the fan plug from the burner.
The unit should shut down within three seconds, proving
operation of the pressure switch.

14.5 User Instructions

After satisfactory testing, ensure that the client is fully
aware of the operation of the system. Bring this manual to

Description

Part Number

Connector male - Lockout Indicator

91324000

Connector female - Lockout Indicator

91324001

Wire Blue 12"

91300011

Wire Brown 12"

91300012

Description

Part Number

Connector male - Volt Free

91324000

Connector female - Volt Free

91324001

Wire Blue 7"

91300004

Wire Brown 7"

91300005

Wire Yellow 12"

91300003

Screw #8 x 3/8 Hex Wshr PHH Type 23

94961406

Base relay P2RF05E

C1050B

Relay G2R1-SN IMO 220 V 10 A

C1049B