Caution – Roberts Gorden Vacuum Assisted Linear User Manual

Page 60

Advertising
background image

B

LACKHEAT

®

I

NSTALLATION

O

PERATION

AND

S

ERVICE

M

ANUAL

54 of 74

Figure 34: Gas Connection with Stainless Steel Flex Connector

INCORRECT POSITIONS (WRONG INSTALLATION)

Heater Movement

Heater Movement

Heater Movement

Heater Movement

CORRECT POSITIONS

Correct position with flex connector not supplied by Roberts-Gordon.

Burner

Stainless Steel Flexible Connector

supplied by Roberts-Gordon 1000 mm Long

Minimum Bend Radius 140 mm

Shut-Off Valve

Flex Line

Connector

45°

45°

545 mm

minimum

Gas Supply Pipe

Flexible Gas Hose

1000 mm length

300 mm

Shut-Off Valve
(included with gas
hose) must be parallel
to burner gas inlet. The
80 mm displacement
shown is for the cold
condition. This
displacement may
reduce when the
system is fired.

80 mm
max. displacement

Side View

Heater Movement

CAUTION

Product Damage Hazard

Hold gas nipple securely with pipe wrench
when attaching gas hose.

Failure to follow these instructions can result
in product damage.