18.9 Burner Specifications

Figure 37: Linear and U-Tube Specifications

*Only available in Multiburner. **Based on Gross Caloric Value.

Natural G20:

8.7 mbar

3.5 in wg

Natural G25:

11.1 mbar

4.5 in wg

Natural G25 BH 55*:

9.5 mbar 3.8 in wg

18.9.1 Standard
Burner Specifications

BH15

BH20

BH25

BH30

BH35

BH40

BH45

BH50

BH55*

Burner Airplate
ID Number

20

15

12

6

7

9

10

11

19

Jet Numbers -
Natural G20 & 25

#30

3.8 mm

#19

4.7 mm

#9

#3

#2

B

E

6.8 mm (G25)

Jet Numbers -
Propane/Butane

#46

2.3 mm

#37

#33

3.1 mm

3.3 mm

#29

#26

#24

Jet Numbers -
Pressure Couple

1.95 mm 2.25 mm 2.5 mm

2.7 mm

2.9 mm

3.2 mm

3.25 mm 3.4 mm -

Gas Consumption**
Natural G20 (m

3

/h)

1.43

1.91

2.38

2.86

3.36

3.81

4.29

4.77

5.25

Gas Consumption**
Natural G25 (m

3

/h)

1.66

2.22

2.77

3.32

3.88

4.43

4.99

5.54

6.09

Gas Consumption**
Propane (m

3

/h) [kg/h]

0.56
[1.07]

0.75
[1.43]

0.94
[1.79]

1.13
[2.15]

1.32
[2.50]

1.51
[2.86]

1.69
[3.22]

1.88
[3.58]

2.07 [3.94]

Gas Consumption**
Butane (m

3

/h)

0.43

0.57

0.72

0.86

1.00

1.15

1.29

1.43

1.57

Governor Pressure
Butane (mbar)

21.4

19.7

19.2

17.4

18.2

17.9

16.9

18.4

18.3

Governor Pressure
Butane (in wg)

8.6

7.9

7.7

7.0

7.3

7.2

6.8

7.4

7.3

Governor Pressure
Propane (mbar)

26.1

26.1

26.1

27.4

26.1

28.6

28.6

26.1

26.1

Governor Pressure
Propane (in wg)

10.5

10.5

10.5

11.0

10.5

11.5

11.5

10.5

10.5

Fan

Damper

Swirler*

Plan View

Reflector

171 mm

End View

Internal Swirler*

273 mm

317
mm

Tube Length

Tube Length

Fan Tube

U-Tube

Plan View

Fan

Burner Tube

Burner Tube

100 mm

100 mm

Damper

*Swirler must always be located in Fan Tube.