68 of 74 troubleshooting flow chart (multiburner) – Roberts Gorden Vacuum Assisted Linear User Manual

Page 74

Advertising
background image

B

LACKHEAT

®

I

NSTALLATION

O

PERATION

AND

S

ERVICE

M

ANUAL

68 of 74

Troubleshooting Flow Chart (Multiburner)

No

Ye

s

Do the burners turn off

when the call for heat ends?

Check the

control panel.

No

Ye

s

Ye

s

No

No

Ye

s

Ye

s

Consult venting and wiring

sections of this manual for reversal instructions.

Follow burner check

procedure given above.

Manifold ID/ID Connectors may be installed improperly

.

High temperature silicone sealant should be used at

all connections.

Is the rotation of the pump

motor correct?

Are there any "dead" burners

in a branch?

Is the vacuum setting

too low?

Adjust system for proper

vacuum. See

Specification Section.

Is the system leaking water?

No

No

No

No

No

Ye

s

Ye

s

No

No

Ye

s

No

Ye

s

Ye

s

Ye

s

No

No

Ye

s

Ye

s

No

Ye

s

No

Ye

s

Ye

s

Ye

s

Ye

s

No

Do all burners light?

W

ere the gas lines

purged of air correctly?

Is there sufficient inlet gas pressure (See Specification Section) during ignition?

Purge Lines.

Measure voltage on valve terminals. Is there 230 V

during ignition time?

Check gas line stop cock. Check gas supply at meter

.

Contact gas company

.

Are the wires connecting the automatic control unit OK?

Replace automatic

control unit.

Check for the proper jet and air plate inside the

burner

.

Is the gas outlet pressure

in accordance with

Specifications Section

of this manual?

Is there gas outlet pressure

available during the

ignition period?

Replace/Correct wires.

Adjust the governor

pressure.

Replace solenoid

coil.

Ignition module may have failed. Replace module.

Is the insulation on the electrode/sensor leads

OK?

Replace/Correct

Wires.

Re-establish connections.

Is the wiring at the module properly

connected?

Are the Live and Neutral

reversed?

Reverse polarity

.

Is the continuity of the earth wire established?

Re-establish continuity

.

Do the burners

stay on?

TROUBLESHOOT ENDS. If problems persist, contact

Roberts-Gordon at

Tel: +44 (0)121 506 7700 or Fax: +44 (0)121 506 7701 or online at www

.rg-inc.com