SECTION 14: OPERATION

Figure 35: Sequence of Operation Chart

NOTE: If the heater operates for more than 24 hours continuously, the ignition module will automatically recycle the
burner to ensure that all safety functions are still in working condition.

14.1 Heater Lockout Indication (Optional)

In case of flame loss during operation of the heater, the
burner control unit goes to lockout mode after three
ignition trials. At this stage a signal or closed relay will
enable the ROBERTS GORDON

®

controller, BMS

system, etc. to indicate precisely which heater has failed.
This can be done by two options.

Cut/Pinch Hazard

Wear protective gear
during installation,
operation and service.

Edges are sharp.

WARNING

Failure to follow these instructions can result in death, electric shock, injury or property damage.

Burn Hazard

Allow heater to cool
before service.

Tubing may still be hot
after operation.

Explosion Hazard

Turn off gas supply to
heater before service.

DANGER

Electrical Shock Hazard

Disconnect electric
before service.

More than one
disconnect switch may
be required to
disconnect electric from
heater.

Heater must be
connected to a properly
grounded electrical
source.

P

P

Fan Neon

Burner Neon

Neon

Ignition

Gas

Valve

Flame
Sensing

Pressure
Switch

Fan

Thermostat

KEY TO

SYMBOLS

T0

T1

T2

T3

T4

T5

T6

T7

10 sec

Tp

40 sec max.

Interruption of main

Tp

10 sec

Ts

10 sec

flame sensing

11 sec typical

T8

Lockout Alarm
Signal (optional)

Burner Lockout

signal received after

3 ignition trial

failures