Automatic Clock Adjustment Error Processing

Section 5-4

Note

For details on other error log information, refer to the Operation Manual, Con-
struction of Networks: SECTION 8 Troubleshooting
.

5-4-3

Error Log Error Codes for the Automatic Clock Adjustment
Function

When an error occurs while the Ethernet Unit is operating, the error code,
detailed error code, and time the error occurred are saved in the error log.
The following table provides a list of the error codes.

The error log can be read by sending FINS commands to the Ethernet Unit or
by using the mail receive function and specifying the ErrorLogRead com-
mand.

Error

code

Meaning

Detailed error code

Correction

EEPROM

1st byte

2nd byte

021A

Logic error
in setting
table

00

01: Data link
table

02: Network
parameters

03: Routing
tables

04: Setup

05: CPU Bus
Unit Words
(CIO/DM)

Recreate the data
specified by the
2nd byte of the
detailed error
code.

Saved

03C1

Server set-
ting error

00: DNS
01: SMTP
02: POP3
03: SNTP

01: IP address

02: Host name

03: Port number

04: Other
parameters

Set the server
settings correctly
based on the
information in the
detailed error
code.

---

03C4

Server
connection
error

00: DNS

01: SMTP

02: POP3

03: SNTP

01: Specified
host does not
exist

02: No service
at specified host

03: Timeout

04: Closed uni-
laterally by host

05: Cannot con-
nect because
account infor-
mation does not
match

06: Host name
resolution error

07: Transmis-
sion error

08: Reception
error

09: Other error

Take either of the
following mea-
sures.

• Correct the set-

tings for each
server.

• Inspect the com-

munications
path (Ethernet
Unit, cable con-
nections, hub,
router, server),
and correct the
situation that is
causing the
error.

---