Using Socket Services by Manipulating Dedicated Control Bits

Section 6-7

If the Remote IP Address is set to 0, a connection can be made to any remote
node and the remote IP address of the node that is connected will be stored
as the Remote IP Address in the Socket Service Parameter Area. If a specific
remote I/O address is set, then a connection can be made only to the node
with the specified address.

If the Remote TCP Port No. is set to 0, a connection can be made to any
remote node regardless of the TCP port number it is using. If a specific
remote TCP port number is set, then a connection can be made only to a
node using the specified TCP port number.

Remote UDP/TCP Port No.

Specify the UDP or TCP port number used by the remote device.

• This parameter is not used when making a receive request for a UDP

socket. The remote UDP/TCP port number will be stored with the
response data and will be written as the Remote UDP/TCP Port No. in the
Socket Service Parameter Area.

• When opening a passive TCP socket, the combination of the remote IP

address and the remote TCP port number can be used to affect process-
ing as shown in the table for the Remote IP Address, above. If the Remote
UDP/TCP Port No. is set to 0, the UDP/TCP port number of the remote
device will be written as the Remote UDP/TCP Port No. in the Socket Ser-
vice Parameter Area.

Time Out Time

Set the time limit in units of 0.1 s for completion of communications from the
time that the Receive Request Switch (TCP or UDP) or the TCP Passive
Open Request Switch is turned ON. A response code of 0080 hexadecimal
(timeout) will be stored if communications time out. If 0 is set, the requested
service will not be timed.

Number of Bytes to Send/Receive

Send the number of bytes to be sent or the number of bytes to receive. When
the transfer has been completed, the actual number of bytes that have been
sent or received will be written here.

Send/Receive Data Address

Specify the address of the first word to send or the address of the first word
where data is to be received. Always set the bit number to 00 hexadecimal.

The following specifications can be used.

Area

Word address

Area

designation

(hexadecimal)

Word address

(hexadecimal)

CIO, HR,
and AR
Areas

CIO

0000 to 6143

B0

0000 to 17FF

HR

H000 to H511

B2

0000 to 01FF

AR

A448 to A959

B3

01C0 to 03BF

DM Area

DM

D00000 to D32767

82

0000 to 7FFF

EM Area

Bank 0

E0_00000 to E0_32767

A0

0000 to 7FFF

:

:

:

:

Bank C

EC_00000 to EC_32767 AC

0000 to 7FFF

Offset

Area
designation

Leftmost 2 digits
of word address

Rightmost 2 digits
of word address

Bit number
(always 00 Hex)

15

8

7

0

+6

+7