Settings required for the mail send function, 4-2 settings required for the mail send function – Omron CS CJ1W-ETN21 User Manual

Page 43

Advertising
background image

19

Using the Mail Send Function

Section 2-4

become effective. Verify that it is safe for the Ethernet Unit to restart before
transferring the settings data.

2-4-2

Settings Required for the Mail Send Function

The following Unit settings must be made when using the Mail Send Function.

CX-

Programmer

Unit Setup

Tab

Setting

Setting requirement

Reference

SMTP

Server specification
type

Required.

1-4 Common
Protocol Settings

IP Address

One or the other is required, depending on the Server specifi-
cation type
setting.

Host name

Port No.

Rarely required (when a setting other than the default setting of
25 is required).

Local mail address

Required.

Use POP before
SMTP

Required when the account must be authenticated with POP3
before sending mail.

POP
(See note 1.)

Server specification
type

Required.

IP Address

One or the other is required, depending on the server specifica-
tion method setting.

Host name

Port No.

Rarely required (when a setting other than the default setting of
110 is required).

Account Name

Required when the account name is different from the name up
to the @ symbol in the e-mail address.

Mail password

Required.

Server access inter-
val time

Optional (Change when the default setting of 5 minutes is unac-
ceptable.)

DNS
(See note 2.)

IP Address

Required.

Port No.

Rarely required (when a setting other than the default setting of
53 is required).

Retry timer

Optional (Change when the default setting of 10 seconds is
unacceptable.)

Mail Address

Mail address 1

At least one e-mail address must be entered (mail address 1 or
2).

page 21

Mail address 2