47

Remote Mail Command Details

Section 3-4

UMBackup (User Memory Backup)

Function

Backs up (saves) the CPU Unit's user program in the CPU Unit's EM file
memory or a Memory Card mounted in the CPU Unit.

Command Format Details

Response Format

Subject: UMBackup

Notation

Description

Omission

Body: Para1:Destination folder

name

Example)

Specifying subdirectory OMRON in
the Memory Card:

Para1:MEMCARD\OMRON

Specifies the destination folder in
which the user program will be
saved.

• MEMCARD specifies the Memory

Card's root directory.

• EM specifies the EM file memory's

root directory.

Note If this parameter is omitted,

the default destination is the
Memory Card's root directory.

Can be omitted.

Para2:File name

Example)

Specifying USER.OBJ:

Para2:USER.OBJ

Specifies the name of the file in
which the user program data will be
saved.

Note If this parameter is omitted,

the default file name is
AUTOEXEC.OBJ.

Can be omitted.

Para3:Overwrite=OK or NG

Example)

Allowing existing file to be overwrit-
ten:

Para3:Overwrite=OK

Specifies whether or not an existing
file may be overwritten.

• To allow an existing file with the

same filename to be overwritten,
enter "Overwrite=OK".

• To prevent an existing file with the

same filename from being overwrit-
ten, enter "Overwrite=NG".

Note If this parameter is omitted,

overwriting is prohibited.

Can be omitted.

Attached file: None

Subject: Re:UMBackup

Response contents

Description

Body: Response Code:

@@@@

Refer to 3-4-2 Response List.

Response Status:

@@@@

Refer to 3-4-2 Response List.

> Para1:Destination folder name

Included only if this parameter was specified.

> Para2:File name

Included only if this parameter was specified.

> Para3:Overwrite=OK or NG

Included only if this parameter was specified.

Attached file: None

Advertising