Using Socket Services with CMND(490)

Section 6-8

6-8-9

UDP/IP Communications Programming Example

The following programming example illustrates transferring 100 bytes of data
between an Ethernet Unit and a host computer using UDP/IP
communications.

For the UDP connection, the Ethernet Unit uses a PASSIVE OPEN and the
host computer uses an ACTIVE OPEN.

System Configuration

The system configuration for the program example and the Ethernet Unit
system setup are shown below.

Basic Operations

• CIO 000000 is turned ON to request opening a UDP socket from the

Ethernet Unit.

• CIO 000001 is turned ON to request closing the UDP socket from the

Ethernet Unit.

• CIO 000002 is turned ON to request sending data from the Ethernet Unit.

Data (100 bytes) is sent beginning at D02008.

• CIO 000003 is turned ON to request receiving data from the Ethernet

Unit. The data that is received (100 bytes) is stored beginning at D04025.

• One of the bits between CIO 000100 and CIO 000103 will turn ON if an

error occurs. Refer to 6-7-5 Socket Service Request Switches for informa-
tion on errors. The following areas can be used to access details about
errors:

CMND(490) response codes
Response codes in results storage area
Network Communications Error Flags (A21900 to A21907)
Completion codes (A203 to A210)

Host computer

Ethernet Unit

IP address: 196.36.32.55
Port number: 4096

IP address:

196.36.32.101

Port number:

4096

FINS network address:

01 Hex

Node address:

01 Hex

Unit number:

10 Hex

PLC