Remote Mail Command Details

Section 3-4

FinsSend (FINS Command Send)

Function

Requests execution of the specified FINS command by the Ethernet Unit.

Command Format

Response Format

3-4-2

Response List

Subject: FinsSend

Notation

Description

Omission

Body: Para1:FINS header

Example)

Specifying DNA=01, DA1=02, and
DA2=00:

Para1:010200

Enter the desired FINS header val-
ues for DNA, DA1, and DA2.

Note If this parameter is omitted, a

parameter error will occur.

Cannot be omitted.

Para2:Command code and
parameter

Example)

Specifying 0501:

Para2:0501*

Enter the command code and
parameter.

*: Always specify this as a termina-
tor.

Note If this parameter is omitted, a

parameter error will occur.

Cannot be omitted.

Attached file: None

Subject: Re:FinsSend

Response contents

Description

Body: Response Code:

@@@@

Refer to 3-4-2 Response List.

Response Status:

@@@@

Refer to 3-4-2 Response List.

-- (FINS header) --

The FINS response is entered in the e-mail body.

-- (Response data) --

The FINS response is entered in the e-mail body.

Attached file: None

Response

Code

Response Status

Description

0000

Normal completion

Command completed normally.

F101

E-mail size exceeds than the
maximum size.

The e-mail is too large.

F102

E-mail address error

Specified e-mail address is invalid.

F103

Invalid command

Specified command is invalid.

F104

Protected (Command type)

Specified command is disabled in the
protection settings.

F105

Invalid subject

Specified subject is invalid.

F201

Invalid parameter

Specified parameter is invalid.

F301

Decoding error

Decoding error

F302

Invalid attached file

Attached file is invalid.

F303

Attached file does not exist

No attached file

Advertising