Omega ILD44-UTP User Manual

Page 25

Advertising
background image

21

Input Type (Process)

ENTER INPUT TYPE MENU:

Press

a

1) Press

a, if necessary, until CNFG prompt appears.

Press

d

2) Display advances to

INPT Input Menu.

Press

d

3) Display flashes

T.ç, RTD or PROC (Thermocouple, RTD or

Process). If the displayed input type is

PROC, press a to skip to

step 6 (

PROC stops flashing).

PROCESS SUBMENU:

Press

b

4) Scroll through the available selection to

PROC (flashing).

Press

d

5) Display shows

STRD stored message momentarily and then

PROC (not flashing).

Press

d

6) Display flashes previous Process type selection. i.e.

0-10

(see below for Process types selection).

Press

b

7) Scroll through the available Process types to the selection of
your choice.

Press

d

8) Display shows

STRD stored message and then advances to

RDG Reading Configuration Menu.

Process Types: 100 mV 1 V

10 V

0 – 20 mA

Display:

0-0.1

0-1.0

0-10

0-20

For 4-20 mA Input select 0-20 mA then adjust the Input/Reading accordingly.
To adjust 4-20 mA input, see example under INPUT/READING submenu. The
factory preset value is 4-20 mA.

3.2.5 Reading Configuration

Figure 3.4 Flow Chart for Reading Configuration Menu

It is recommended that you put the
controller in the Standby Mode for any
configuration change other than Setpoints &
Alarms.