Omega ILD44-UTP User Manual

Page 45

Advertising
background image

41

RESET SETUP SUBMENU:

Press

d

33) Display flashes 1

st

digit of the previous I

REST Reset value.

Press

b & c 34) Press b and c buttons to enter a new “Reset” value.

Press

d

35) Display shows

STRD stored message momentarily and then

advances to

RATE only, if it was changed, otherwise press a to

advance to

RATE Rate Setup Submenu.

Reset unit is in seconds 0-3999.

RATE SETUP SUBMENU:

Press

d

36) Display flashes 1

st

digit of previous D

RATE Rate value.

Press

b & c 37) Press b and c buttons to enter a new RATE value.

Press

d

38) Display shows

STRD stored message momentarily and then

advances to the

CYCL only, if it was changed, otherwise press a

to advance to

CYCL Cycle Time submenu for RTD and

Thermocouple types.

Rate unit is in seconds 000.0-399.9.

If the Output 1 is Analog Option the display skips to Damping
Factor.

CYCLE TIME SUBMENU:

Press

d

39) Display flashes 1

st

digit of the previous

CYCL Cycle Time

value.

Press

b & c 40) Press b and c buttons to enter a new “Cycle Time” value.

(1 to 199 seconds)

Press

d

41) Display shows

STRD stored message momentarily and then

advances to

DPNG only, if it was changed, otherwise press a to

advance to

DPNG Damping Factor Submenu.

A Cycle Time selected between 1 and 199 seconds determines the total On/Off
time of each proportional cycle. For example, a 15 second cycle time means that
every 15 seconds the output will turn on for part or all of the cycle. For Relay
control outputs, do not select a cycle time of less than 7 seconds or the relays’
lifetime will be shortened. For a cycle time of less than 7 seconds select SSR or
DC pulse. Use an external SSR with the DC pulse option for higher currents
(higher than 1 Amp).