Omega ILD44-UTP User Manual

Page 38

Advertising
background image

34

LOOP BREAK TIME VALUE SUBMENU:

Press

d

7) Display flashes 1

st

digit of previous Loop Value.

Press

b & c 8) Press b and c buttons to enter a new Loop Value

(0 to 99.59).

Press

d

9) Display shows

STRD stored message momentarily and then

advances to

R.ADJ Reading Adjust Submenu.

Loop Break Time Value allows the user to determine the time interval in MM:SS
(from zero to 99 minutes and 59 seconds) that the Process Value changes at
least 10 counts or if the Input Type is either RTD or Thermocouple, the value
changes 4° Fahrenheit or 2° Celsius. At the specified time interval, if the process
value change is less than the stated rate, flashing

B.TIM will be displayed, the

output 1 will be de-energized, and Alarm 1 energized. Loop break time will be
disabled when the Process Value (PV) enters the control band.

C.J. READING ADJUST SUBMENU:

Press

d

10) Display flashes 1

st

digit of previous reading adjust value.

Press

b & c 11) Press b and c buttons to enter a new Reading Adjust value

(-1999 to 9999).

Press

d

12) Display shows

STRD stored message momentarily and then

advances to

SP.DV Setpoint Deviation Menu.

Reading Offset Adjust (C.J.) allow the user to fine tune a minor error of the
transducer, however some applications may require a large offset adjust.
(Displayed Process Value = Measured Process Value ± R.ADJ). R.ADJ is
adjustable between -1999 to 9999.

SETPOINT DEVIATION ENABLE/DISABLE SUBMENU:

Press

d

13) Display advances to Setpoint Deviation

ENBL Enable or DSBL

Disable Submenu and flashes the previous selection.

Press

b

14) Scroll through the available selections:

ENBL or DSBL.

Press

d

15) Display shows

STRD stored message momentarily and then

advances to

CAL.

Menu.

Setpoint Deviation Submenu, if “enabled”, allows changes to Setpoint 1 to be
made automatically to Setpoint 2. This mode is very helpful if the Process Value
changes often. In Setpoint Deviation Mode, set SP2 a certain number of degrees
or counts away from SP1 - this relation remains fixed when SP1 is changed. For
instance: Setting SP1=200 and SP2=20 and enabling

SP.DV means that the

absolute value of SP2=220. Moving SP1 to 300, the absolute value of SP2
becomes 320.

°

Advertising
This manual is related to the following products: