CONTACT CLOSURE SUBMENU:

Press

d

11) Display flashes previous selection. Press

b to N.ç. Normally

Closed or

N.o. Normally Open.

Press

d

12) Display shows

STRD stored message momentarily and then

advances to

AçTV only if it was changed, otherwise press a to

advance to

AçTV Active Submenu.

Normally Open: If this feature is selected, then the relay is "energized" only
when an alarm condition occurs.

Normally Closed: "Fail Safe" Mode. Relay is energized under "normal"
conditions and becomes de-energized during alarm or power failure.

ACTIVE SUBMENU:

Press

d

13) Display flashes previous selection. Press

b to scroll through

the available selections:

ABoV Above, BELo Below, HI.Lo

HI/Low and

BAND Band. (Band is active if _DEV Deviation was

selected).

Press

d

14) Display shows

STRD stored message momentarily and then

advances to

A.P.oN only if it was changed, otherwise press a to

advance to

A.P.oN Alarm Enable/Disable at Power On Submenu.

Above: Alarm 1 condition triggered when the process variable is greater than the
Alarm Hi Value (Low value ignored).

Below: Alarm 1 condition triggered when the process variable is less than the
Alarm Low Value (Hi value ignored).

Hi/Low: Alarm 1 condition triggered when the process variable is less than the
Alarm Low Value or above the Hi Value.

Band: Alarm 1 condition triggered when the process variable is above or below
the "band" set around Setpoint 1. Band equals Hi Value (Low Value ignored). A
"band" is set around the Setpoint by the instrument only in the "Deviation" Mode.