Omega ILD44-UTP User Manual

Page 32

Advertising
background image

28

ALARM ENABLE/DISABLE AT POWER ON:

Press

d

15) Display flashes previous selection. Press

b to ENBL enable

or

DSBL disable.

Press

d

16) Display shows

STRD stored message. momentarily and then

advances to

ALR.L only if it was changed, otherwise press a to

advance to the

ALR.L Alarm 1 Low Value Submenu.

If the alarm is enabled at Power On, the alarm will be active right after
reset. If the alarm is disabled at Power On, the alarm will become
enabled when the process value enters the non alarm area. The alarm is
not active while the process value is approaching Setpoint 1.

ALARM 1 LOW VALUE SUBMENU:

Press

d

17) Display flashes 1

st

digit of previous value. Use

b and c to

enter new value.

Press

b & c 18) Use b and c to enter Alarm 1 Low Value.

Press

d

19) Display shows

STRD storage message momentarily and

then advances to

ALR.H only, if it was changed, otherwise press

a to advance to ALR.H Alarm 1 Hi Value Submenu.

ALARM 1 HI VALUE SUBMENU:

Press

d

20) Display flashes 1

st

digit of previous value. Use

b and c to

enter new value.

Press

b & c 21) Use b and c to enter Alarm1 Hi Value.

Press

d

22) Display shows

STRD stored message momentarily and then

advances to the next menu only, if it was changed, otherwise
press

a to advance to the next menu.