13.6.2 Supported Subpoints

This application contains a predefined set of FLN subpoints (refer to Table 4).
These points are static for this application, and cannot be edited.

Table 4: Supported Subpoints

Point #

Point

Type

Subpoint

Name

Factory

Default

Units

Slope Intercept

On

Text

Off

Text

01 LAO

ADDRESS

99

1

0

02 LAO APPLICATION 2750 –

1

0

03 LAI FREQ

OUTPUT

0

HZ 0.01

0

04 LAI OUTPUT

CUR

0

A 0.01

0

05 LAI OUTPUT

VOLT

0

V 0.1

0

06 LAI SPECIAL

MON

0

-

1

0

07 LAO MON

SELECT

0

-

1

0

08 LAO ACCEL

TIME

50 SEC 0.1

0

09 LAO DECEL

TIME

100 SEC 0.1

0

10

LDO

CMD

FWD.STOP

STOP

– 1 0 FWD

STOP

11

LDO

CMD

REV.STOP

STOP

– 1 0 REV

STOP

12 LAO FREQ

CMD

0

HZ 0.01

0

13 LAO MIN

FREQ

0

HZ 0.01

0

-

-

14

LAO

FREQ JUMP A

32767

HZ

0.01

0

-

-

15

LAO

FREQ JUMP B

32767

HZ

0.01

0

-

-

16 LDI ALARM

OUTPUT

0

1

0 ALARM -

17

LDI RUNNING STOP

– 1 0 RUN

STOP

18

LAO

PID SET PNT

0

PCT

0.01

0

-

-

19 LDO RESET

CMD

0

1

0 RESET -

20 LAO OVRD

TIME

1 HRS 1

0

21

LDI ASD

COMM NO - 1 0 YES

NO

22 LAO OPER

MODE

0

-

1

0

-

-

29 LDO DAY.NIGHT

DAY –

1

0 NIGHT DAY

99 LAO ERROR

STATUS

0

1

0

Notes:

Points not listed are not used in this application.

All points have the same value for English units and SI units.