4 fundamental parameters #2, 5 panel control parameters – Toshiba XLTR-200 User Manual

Page 71

Advertising
background image

70

13.7.4 Fundamental Parameters #2

Parameter

Function / Title

Bank

Mask

Adjustment Range

Multiplier

0034

BASE FREQUENCY #2

0 / 1

FFFF

09C4

∼ 9C40 (25.00 ∼ 400.00)

0.01

0035

MAXIMUM OUTPUT

VOLTAGE #2

0 / 1

FFFF

0000

∼ 0258 (0 ∼ 600)

1

0036

VOLTAGE BOOST #2

0 / 1

FFFF

0000

∼ 012C (0.0 ∼ 30.0)

0.1

0037

ELECTRONIC THERMAL

PROTECT LVL #2

0 / 1

00FF

000A

∼ 0064 (10 ∼ 100)

1

0038

STALL PROTECTION

SELECTION #2

0 / 1

0040

0000: ON

(0)

0040: OFF

(1)

0039

0

STALL PROTECTION

LEVEL #2

0 / 1

00FF

000A

∼ 00D7 (10 ∼ 215)

1

003A

ACCELERATION TIME #2

0 / 1

FFFF

0001

∼ EA60 (0.1~ 6000.0)

0001

∼ EA60 (0.01~ 600.00)

0.1

0.01

003B

DECELERATION TIME #2

0 / 1

FFFF

0001

∼ EA60 (0.1~ 6000.0)

0001

∼ EA60 (0.01~ 600.00)

0.1

0.01

003C

ACC/DEC PATTERN #2

SELECTION

0 / 1

0030

0000: Linear

(0)

0010: Self-adjusting

(1)

0020: S-Pattern #1

(2)

0030: S-Pattern #2

(3)

003D

ACC/DEC #1/#2 SWITCH

FREQUENCY

0 / 1

FFFF

0000

∼ Fmax

0.01


13.7.5 Panel Control Parameters

Parameter

Function / Title

Bank

Mask

Adjustment Range

Multiplier

003E

DIRECTION SELECTION

(FORWARD/REV)

0 / 1

0004

0000: Reverse

(0)

0004: Forward

(1)

003F

STOP PATTERN

SELECTION

0 / 1

0040

0000: Decelerated stop

(0)

0040: Coast stop

(1)

0040

FUNDAMENTAL PARAM

SWITCHING

0 / 1

0004

0000: V/F #1

(1)

0004: V/F #2

(2)

0041

ACCEL/DECEL #1/#2

SELECTION

0 / 1

0008

0000: Accel / decel #1

(1)

0008: Accel / decel #2

(2)

0042

PANEL RESET

SELECTION

0 / 1

0030

0000: All possible

(0)

0010: OL only

(1)

0020: OL, OC only

(2)

0043

PANEL FEEDBACK

CONTROL

0 / 1

0001

0000: Feedback valid

(0)

0001: Feedback invalid

(1)

Advertising