15 motor rating parameters – Toshiba XLTR-200 User Manual

Page 90

Advertising
background image

89

13.7.15 Motor Rating Parameters

Parameter

Function / Title Bank

Mask Adjustment Range

Multiplier

0242

NUMBER OF MOTOR POLES

0 / 1

00FF

0001:

(2)

0002: (4)
0003: (6)
0004: (8)
0005: (10)
0006: (12)
0007: (14)
0008:

(16)

2

0243

MOTOR RATED CAPACITY

0 / 1

FFFF

0001

∼ 270F (0.1 ∼ 999.9)

0.1

0244

MOTOR TYPE

0 / 1

0030

0000:Toshiba EQPIII motor

(0)

0010:Toshiba STD motor

(1)

0020:Other (2)

0245

MOTOR RATED

VOLTAGE

(230 / 460v units)

0 / 1

00FF

0012

∼ 0078 (90 ∼ 600)

5

0246 (575v

units)

001A

∼ 00AC (130 ∼ 860)

0247

MOTOR RATED

FREQUENCY

0 / 1

00FF

0000

∼ 00C8 (0 ∼ 400)

2

0248

MOTOR RATED RPM

0 / 1

FFFF

0000

∼ 270F (0 ∼ 9999)

1

0249

2

AUTO-TUNING ENABLE

0

0008

0000: Auto-tuning disabled

(0)

0008: Auto-tuning enabled

(1)

024A

LOAD MOMENT OF INERTIA

0 / 1

00C0

0000: Small

(0)

0040: Medium

(1)

0080: Large

(2)

00C0: Very large

(3)

Advertising