13.7.7 Special Control Parameters

Parameter

Function / Title

Bank

Mask

Adjustment Range

Multiplier

0069

START-UP FREQUENCY

0 / 1

FFFF

0000

∼ 03E8 (0.00 ∼ 10.00)

0.01

006A

006F

Reserved

0070

END FREQUENCY

0 / 1

FFFF

0000

∼ 0BB8 (0.00 ∼ 30.00)

0.01

0071

RUN FREQUENCY

0 / 1

FFFF

0000

∼ Fmax

0.01

0072

RUN FREQUENCY

HYSTERESIS

0 / 1

FFFF

0000

∼ 0BB8 (0.00 ∼ 30.00)

0.01

0073

ENABLE JUMP

FREQUENCIES

0 / 1

0080

0000: Function OFF

(0)

0080: Function ON

(1)

0074

JUMP FREQUENCY #1

0 / 1

FFFF

0000

∼ Fmax

0.01

0075

JUMP FREQUENCY #1

BANDWIDTH

0 / 1

FFFF

0000

∼ 0BB8 (0.00 ∼ 30.00)

0.01

0076

JUMP FREQUENCY #2

0 / 1

FFFF

0000

∼ Fmax

0.01

0077

JUMP FREQUENCY #2

BANDWIDTH

0 / 1

FFFF

0000

∼ 0BB8 (0.00 ∼ 30.00)

0.01

0078

JUMP FREQUENCY #3

0 / 1

FFFF

0000

∼ Fmax

0.01

0079

1

JUMP FREQUENCY #3

BANDWIDTH

0 / 1

FFFF

0000

∼ 0BB8 (0.00 ∼ 30.00)

0.01

007A

007F

Reserved

0080

PWM CARRIER FREQUENCY

(Note 1)

0 / 1

00FF

0005

∼ 0064 (0.5 ∼ 10.0)

0.1


Note 1: Actual adjustment range depends on inverter rating.