Table 9: Input Terminal Selections

Setting

Value

Data

(Hex)

Function

Setting

Value

Data

(Hex)

Function

0

10C8

R

(reverse run)

28

04AF

Binary bit #6

1

011C

SS1

(preset speed selection)

29

08AF

Binary bit #7

2

021C

SS2

(preset speed selection)

30

10AF

Binary bit #8

3

041C

SS3

(preset speed selection)

31

20AF

Binary bit #9

4

081C

SS4

(preset speed selection)

32

40AF

Binary bit #10

5

20C8

F

(forward run)

33

04CE

No effect

6

201B

RES

(fault reset)

34

01C7

UP/DOWN frequency setting (UP)

7

C0C9

ST

(gate ON/OFF)

35

02C7

UP/DOWN frequency setting
(DOWN)

8

0CC8

JOG selection

36

04C7

UP/DOWN frequency clear

9

081A

Accel / decel #1/#2 selection

37

08C7

PUSH-type RUN key

10

101B

Emergency off

38

10C7

PUSH-type STOP key

11

021B

DC injection braking ON/OFF

39

02B9

No effect

12 041B

Fundamental

parameter

switching (V/F #2)

40

C0C8

Forward/reverse run selection

13

011B

Feedback control ON/OFF

41

20C7

RUN

14

10CE

Pattern run selection #1

42

30C9

Binary data write

15

20CE

Pattern run selection #2

43

0198

[LOCAL/REMOTE] key

16

40CE

Pattern run selection #3

44

0298

[MON] key

17

80CE

Pattern run selection #4

45

0498

[PRG] key

18

02CE

Pattern run continue signal

46

0898

[UP] key

19

01CE

Pattern run step trigger signal

47

1098

[DOWN] key

20

0AC9

JOG forward run

48

2098

[READ/WRITE] key

21

06C9

JOG reverse run

49

4098

[RUN] key

22

10AE

Binary bit #0

50

8098

[STOP/CLEAR] key

23

20AE

Binary bit #1

51

08CE

Commercial power / inverter
switching signal

24

40AE

Binary bit #2

52

40C7

Reserved for option use

25

80AE

Binary bit #3

53

10CB

RR frequency switching input

26

01AF

Binary bit #4

54

20CB

IV frequency switching input

27

02AF

Binary bit #5


Note: