1 command parameters – Toshiba XLTR-200 User Manual

Page 65

Advertising
background image

64

13.7.1 Command Parameters

Parameter

Bit Function Bank

Mask

Adjustment Range

Multiplier

0001 word

Frequency

command 0 FFFF

0.00

∼ 400.00Hz

Actual frequency will be limited by
LL, UL and Fmax.

0.01

0002 0

RUN

command

0

0: Stop
1: Run

1

Reserved

2

Forward

• reverse run

selection

0:

reverse

1: forward

3

Acc/dec #1 / #2
selection

0: Acc / dec #1
1: Acc / dec #2

4

Reserved

5

Reserved

6

Reserved

7

Jog mode selection

0: Normal (acc/dec mode)
1: Jog mode

8

Feedback control

0: Feedback valid
1: Feedback invalid

9

Compulsory

DC

injection braking mode

0: No compulsory DC injection

braking

1: Compulsory DC injection

below DC INJECTION

START FREQUENCY

A

Fundamental
parameter switching

0: V/F #1
1: V/F #2

B

Gate block command
(coast stop command)

0:

Normal

1: Gate block

C

Emergency

off

command

0: Does nothing
1: Emergency off

D

Reset

command

(trip clear)

0: Does nothing
1: Reset

E

Reserved

F

Reserved

0003

word

RS232 command /
frequency selection

0 0003

0000:

FREQUENCY MODE
SELECTION, COMMAND

MODE SELECTION

settings

0001: RS232C commands valid
0002: RS232C frequency valid
0003: RS232C commands and

frequency valid

0004

word

Preset speed run
command

0 000F

0000:

Output

frequency

selected by FREQUENCY

MODE SELECTION

0001

∼ 000F: speeds 1 ∼ 15