1 introduction, As311 overview – Toshiba AS311 User Manual

Page 10

Advertising
background image

8

ASCII Interface Module (AS311)

1. AS311 Overview


1.1 Introduction


The ASCII interface module AS311 (hereafter called AS311) is a general purpose data

communication module for Toshiba’s Programmable Controller PROSEC-T3 (hereafter

called T3). By using the AS311, T3 can communicate with external devices, such as a

micro computer, bar code reader, printer, display device, sensor, etc., through the

serial interface RS-232C or RS-422.


The AS311 has two ports of the serial interface. One port (channel 1) can be selected

either RS-232C or RS-422 by switch setting. The other port (channel 2) is RS-232C

interface. These two ports can be used independently for data receiving and

transmitting.


The transmission is asynchronous (start-stop system).

ASCII is used as the transmission data code.


The figure below shows the typical system configuration.




The maximum number of AS311 that can be controlled by one T3 is not limited by
software. However, this module consumes maximum 1 A of internal 5 Vdc power.
Confirm that the total 5 Vdc consumed current per one power supply module is
within the limit (7 A).

CPU module

T3

Channel 2
RS-232C

Channel 1
RS-232C or RS-422

AS311

NOTE