5. Operation Procedure


5.3 Write sequence for message transmitting


5.3.1

Flag control timing

In case of transmitting a message, the following flags are used for handshaking

between T3 and AS311. These flags are the bits of the I/O registers assigned to the

AS311. Refer to section 4.1.


Write ready

Bit F of XW(n) for channel 1 or XW(n+1) for channel 2

Transmit complete

Bit E of XW(n) for channel 1 or XW(n+1) for channel 2

Transmit error

Bit D of XW(n) for channel 1 or XW(n+1) for channel 2


Transmit start

Bit F of YW(n+2) for channel 1 or YW(n+3) for channel 2


The message transmitting procedure is as follows. It is called “write sequence for

message

transmitting”.



T3

checks

Write ready is ON



T3 writes a message into buffer

memory (transmitting data area)

by WRITE instruction



T3

sets

Transmit start to ON



AS311

resets

Write ready to OFF



Normal transmitting

Transmitting error


AS311 sends out the message and

AS311 sets the error information into

sets

Transmit complete to ON

buffer memory (parameter area) and

sets

Transmit error to ON


T3

resets

Transmit start to OFF

T3 reads the error information from

buffer memory (parameter area)

AS311

resets Transmit complete to

by READ instruction, and resets

OFF, and sets Write ready to ON

Transmit start to OFF


AS311

resets

Transmit error to OFF,

and

sets

Write ready to ON

Advertising