ASCII Interface Module (AS311)

4. Register Configuration


4.1 I/O allocation and I/O registers


The AS311 has the I/O type ‘i X+Y 4W’ for I/O allocation. When the automatic I/O

allocation is performed with mounting the AS311, the following I/O allocation table will

be created in the T3.


(T-PDS screen example - in the case that AS311 is mounted on Slot 0 of Unit 0)



Then, 4 I/O registers, XW(n), XW(n+1), YW(n+2) and YW(n+3), are assigned to the

AS311.

In the above example, XW000, XW001, YW002 and YW003 are assigned.


Note that the I/O type has ‘i’ designation. It means that the T3 will not update the

assigned I/O registers in the batch I/O processing. To read or write data through

the I/O registers, the Direct I/O instruction (FUN235) or the direct I/O designation

(I/IW and O/OW instead of X/XW and Y/YW) is necessary.

The reason of that is because the reading and writing timings are important for

handshaking between T3 and AS311. Refer to section 5.