A.1 specification of the read instruction, Appendix – Toshiba AS311 User Manual

Page 62

Advertising
background image

60

ASCII Interface Module (AS311)

Appendix


A.1 Specification of the READ instruction

FUN 237 Special module data read (READ)

Reads designated range of data from the special module.

Input Execution output
[ A READ B

C ]


Function

This instruction reads data from the buffer memory of the special module that is
designated by operand A, and stores them in T3’s registers starting with operand C.

The transfer source address (buffer memory
address) is designated by operand B.

The transfer size (number of words) is
designated by operand B+1.

Operand

Index

Constant

Device

Register

Opr Name

X Y S L R Z T. C. I O

XW

YW

SW

LW

RW

W T C D F IW O

W

I J K

A Special

module

B Transfer

parameter

C Top

register

of destination


Program example


R0000

[ XW000 READ RW010

D0100 ]


When R0000 is ON, the buffer memory data of the size indicated by RW011, starting with the
address indicated by RW010 of the special module allocated to XW000, are read and stored in
D0100 and after.

The maximum number of words to be read is 256 words.


XW000 special module

T3


RW010 20

Buffer memory

RW011 16


20 1234

READ

D0100 1234


35 5678

16 words

D0115 5678

Input Action Output

ERF

OFF No

execution

OFF

ON Normal

execution

ON

Error (see Note 2)

ON

ON

Advertising