3.11 Pulse Rate

This applies to the Relay Pulsed Output option only. Units with this option provide pulses to
indicate power consumption (kWh).

This screen allows setting of the kWh pulse rate divisor. On a two part DIS 1540/Integra 1560,
this screen will set the pulse rate for the kvarh pulse relay (where fitted) also. By default, the unit
produces one pulse per kWh. Changing this divisor changes the output pulse rate, as follows:

Divisor

One pulse per:

1

1 kWh

10

10 kWh

100

100 kWh

1000

1000 kWh (DIS1540 with 1560/1580 only)

Press >> to accept the currently displayed value. The next

Set-up screen will then appear.

To change the pulse rate divisor, press

.

Use the

key to scroll the value through the available values

1, 10, 100, 1,000. If the maximum power is greater than 3.6
megawatts, the range of divisors will be restricted to force an
upper limit to the number of pulses/hour of 3600.

Select the required divisor and press >> to confirm your
selection. The Confirmation screen will appear.

To change the value again, press

. The Edit screen will

reappear.

To accept the displayed value, press >>. The next Set-up screen
will appear.

30

Integra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03