Metasys n2 application – Tyco 1540 User Manual

Page 64

Advertising
background image

62

Integra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03

METASYS N2 application

Integra 1560/1580 Point Mapping table

Address

Parameter Description

Units

1

Voltage 1

Volts

2

Voltage 2

Volts

3

Voltage 3

Volts

4

Current 1

Amps

5

Current 2

Amps

6

Current 3

Amps

7

Voltage average

Volts

8

Current average

Amps

9

Power (Watts) Sum

kW

10

VA Sum

kVA

11

var Sum

kvar

12

Power Factor average

13

Frequency

Hz

14

Active Energy (Import)

kWh

15

Reactive Energy (Import)

kvarh

16

Watts Demand (Import)

kW

17

Maximum Watts Demand (Import)

kW

18

Amps Demand

Amps

19

Maximum Amps Demand

Amps

20

Voltage L1-L2 (calculated)

Volts

21

Voltage L2-L3 (calculated)

Volts

22

Voltage L3-L1 (calculated)

Volts

23

Neutral Current

Amps

24

Active Energy (Import)

GWh

25

Reactive Energy (Import)

Gvarh

The following parameters are available only on the Integra 1540

26

THD V1

%

27

THD V2

%

28

THD V3

%

29

THD I1

%

30

THD I2

%

31

THD I3

%

32

THD Vmean

%

33

THD Imean

%