Design considerations

When integrating the Crompton equipment into a Metasys Network, keep the following
considerations in mind.

• Make sure all Crompton equipment is set up, started and running properly before attempting

to integrate with the Metasys Network.

• A maximum of 32 devices can be connected to any one NCM N2 Bus.

Vendor Address

1-247 (Limited by co-resident Modbus protocol)

Port Set-up
Baud Rate

9600

Duplex

Full

Word Length

8

Stop Bits

1

Parity

None