Tyco 1540 User Manual

Page 52

Advertising
background image

of IEC688:1992

Error in measurement when a

Twice the error allowed at the end of the reference

measurand is within its measuring

range adjacent to the section of the measuring

range, but outside its

range where the measurand is currently operating

reference range.

or being tested.

4.3.4 Reference conditions

Reference conditions of measurands and, where applicable, components of the measurand

Values of measured quantities, and of components of measured quantities, where the intrinsic
(headline) errors for the measured quantities apply.

Voltage

50 .. 100% of nominal

Current

10 .. 100% of nominal

Frequency

Nominal ±10%

Active power (Watt)

10 .. 100% of nominal

Voltage

Nominal ±2%

Current

10 .. 100% of nominal

Active power factor

1 .. 0.8 leading or lagging

Reactive power (VAr)

10 .. 100% of nominal

Voltage

Nominal ±2%

Current

10 .. 100% of nominal

Reactive power factor

1 .. 0.8 leading or lagging

Apparent Power (VA)

10 .. 100% of nominal

Voltage

Nominal ±2%

Current

10 .. 100% of nominal

Power factor

1 .. 0.8 leading or lagging

Voltage

Nominal ±2%

Current

40 .. 100% of nominal

4.3.5 Reference conditions of influence quantities

Values that quantities which affect measurement errors to a minor degree have to be for the
intrinsic (headline) errors for measured quantities to apply.

Ambient temperature

23°C

Input frequency

50 or 60 Hz ±2%

Input waveform

Sinusoidal (distortion factor 0.005)

Auxiliary supply voltage

Nominal ±1%

Auxiliary supply frequency

Nominal ±1%

Auxiliary supply distortion factor

0.05

Magnetic field of external origin

Terrestrial flux

50

Integra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03