Tyco 1540 User Manual

Page 50

Advertising
background image

4.2.7 Safety

IEC1010-1 (BSEN 61010-1) Permanently connected use, Normal Condition Installation category
III, pollution degree 2, Basic Insulation 720V RMS maximum. Auxiliary circuits (12-48V auxuliary,
communications, relay and analogue outputs, where applicable) are separated from metering
inputs and 100-250V auxiliary circuits by at least basic insulation. Such auxiliary circuit terminals
are only suitable for connection to equipment which has no user accessible live parts. The
insulation for such auxiliary circuits must be rated for the highest voltage connected to the
instrument and suitable for single fault condition. The connection at the remote end of such
auxiliary circuits should not be accessible in normal use. Depending on application, equipment
connected to auxiliary circuits may vary widely. The choice of connected equipment or
combination of equipment should not diminish the level of user protection specified.

4.2.8 Insulation

Dielectric voltage withstand test 3.25kV RMS 50Hz for 1 minute between all isolated
electrical circuits

4.2.9 Environmental

Operating temperature

-20 to +70°C

Storage temperature

-20 to +80°C

Relative humidity

0 .. 95% non condensing

Shock

30g in 3 planes

Vibration

10 to 15 Hz @ 1.5 mm peak-peak
15 to 150 Hz @ 1.0g

Enclosure integrity (front face only)

IP54

Harmonic distortion

max 50% THD up to 15th harmonic

4.2.10 Enclosure

Style ANSI

C39.1

Material

Polycarbonate front and base, steel case

Terminals

6-32 UNC slotted barrier type

Weight

1.3kg

4.3 Display/Tranducer Combined 1000 and 1540

See section 4.3.16 for specifications particular to the 1540

4.3.1 Inputs

Nominal input voltage (a.c. rms)

57.7 to 600V L-N (single phase)
100 to 600V L-L (3 wire)
57.7 to 346V L-N (4 wire)

System PT/VT primary values

1V to 400KV

48

Integra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03