LOV

121 - 240V L-L (70.1 - 139V L-N)

MIV

241 - 480V L-L (140 - 277V L-N)

HIV

481 - 600V L-L (277 - 346V L-N)

(Voltage range is defined by factory build option.)

Nominal input voltage (a.c. rms)

57.7 to 346V L-N
100 to 600V L-L

System PT/VT primary values

1V to 400 kV

Max continuous input voltage

120% of nominal (up to 720 V max.)

Max short duration input voltage

Twice nominal (1s application repeated 10 times at
10s intervals)

Nominal input voltage burden

0.2 VA approx. per phase

Nominal input current

1 or 5 A a.c. rms

System CT primary values

Standard values up to 9999 Amps

(5 A secondaries)
(1 A on application)

Max continuous input current

120% of nominal

Max short duration current input

20 times nominal (1s application repeated 5 times at
5 min intervals)

Nominal input current burden

0.6 VA approx. per phase

4.2.2 Auxiliary Power Supply

The unit can be powered from an auxiliary a.c. or d.c. supply that is separate from the metered
supply. Versions of the unit are available to suit 100-200V 45-65 Hz a.c./d.c. and 12-48V d.c
supplies.

4.2.2.1 High Voltage version

Standard supply voltage

100 to 250V a.c. nominal ±15% (85V a.c. absolute
minimum to 287V a.c. absolute maximum) or 100V to
250V d.c. nominal +25%, -15% (85V d.c. absolute
minimum to 312V d.c. absolute maximum)

a.c. supply frequency range

45 to 66 Hz or 360 to 440 Hz (Model 0440)

a.c. supply burden

3W

4.2.2.2 Low Voltage version

d.c.supply

12 to 48V d.c.. nominal +25%, -15% (10.2V d.c. absolute
minimum to 60V d.c. absolute maximum)

d.c. supply burden

3W

46

Integra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03