4 Specification

The parameters listed in this section apply only to those models that can measure those
parameters.

4.1 Display Only Versions

4.1.1 Input

RS485

Dedicated to Crompton Integra transducers

4.1.2 Auxiliary Power Supply

The unit can be powered from an auxiliary a.c. or d.c. supply that is separate from the metered
supply. Versions of the unit are available to suit 100-250V 45-65 Hz a.c./d.c. and 12-48V d.c
supplies.

4.1.2.1 High Voltage version

Standard nominal supply voltages

100 - 250V a.c. nominal ± 15% (85V a.c. absolute
minimum to 287V a.c. absolute maximum) or
100 - 250V d.c. nominal -15%, +25% (85V d.c. absolute
minimum to 312V d.c. absolute maximum)

A.C. supply frequency range

45 to 66 Hz or 360 to 440 Hz (Model 0440)

A.C. supply burden

4VA approx.

4.1.2.2 Low Voltage version

D.C.supply

12 - 48V d.c. -15% + 25% (10.2V d.c. absolute minimum
to 60V d.c. absolute maximum)

D.C. supply burden

4VA approx.

4.1.3 EMC Standards

EMC Immunity

EN61326 for Industrial Locations to performance
criterion A

EMC Emissions

EN61326 to Class A - Industrial

44

Integra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03