1 Introduction

This manual provides operating instructions for the Crompton Switchboard Integra series of
Digital Metering Systems. Some versions of the Integra incorporate the metering transducer
that provides the interface for the measurement of power supply parameters such as voltage,
current, power, frequency etc. In other versions, the display and transducer are separate,
interconnected units. The display allows the user to set up metering transducer parameters
and to monitor the measurements. Some Integra models can be supplied as either an integral
or display-only version, while others are only available in one format. This manual provides
user instructions.

A separate leaflet provides installation instructions.

Table1 lists the various models of Integra and shows their distinctive characteristics.

Table 1 Summary of Integra models

Model

V

A

F

PF

kW kWh THD Analogue

Serial

Pulse

Freq

0240

V

F

45-65 Hz

0340

V

A

45-65 Hz

0440

V

A

F

360-400 Hz

0640

V

A

F

45-65 Hz

1000

V

A

F

PF

kW

kWh

RS485

Pulse

45-65 Hz

option

option

1540

V

A

F

PF

kW

kWh THD Analogue

RS485 Pulse

option*

option

option

45-65 Hz

* When used with an 1560/80 transducer that includes analogue options.

Voltage and current readings are true RMS, up to the 15th harmonic (31st for 1560/80
transducer).

The unit can be powered from an auxiliary a.c. or d.c. supply that is separate from the metered
supply. Versions of each model are available to suit 100-250V 45-65 Hz a.c./d.c. and 12-48V d.c
nominal supplies.

In this manual, the graphic

0240

0340

0440

0640

1000

1540

is used to show the models to which a screen applies. Boxes are greyed out to show models
that do not have that type of screen.

0240

0340

0440

0640

1000

1540

This example indicates that the screen only applies to Models 1000 and 1540.

0240

0340

0440

0640

1000

1540 Option

This indicates that the screen is an option on models 1000 and 1540.

Important safety information is contained in the accompanying installation instructions.

Installers must familarise themselves with this information before installation.

Integra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03