Electrical specifications: invert mode – Xantrex Technology PROsine 2.0 User Manual

Page 122

Advertising
background image

Specifications

A–2

445-0089-01-01

Electrical Specifications: Invert Mode

DC Input

Operating voltage range

10.0V–16.0V

Safe non-operating voltage range

0–18Vdc

Nominal current at full load

200A

AC Output

Output voltage

117Vac

Continuous power

2.0kW, 2.0kVA to 40°C max. ambient

Surge power

4.5kW for 5s

Max short-circuit current

55Arms, 55Apk

Frequency

60.0Hz ±0.05%

Wave shape

Sine

THD (over load range of 0–2.0kW
resistive)

≤2%

Power derating above 40°C ambient temp

See “Invert Power Derating vs. Ambient
Temperature” on page A–6.

Peak efficiency

≥87%

Full load efficiency

≥83%

Other

Load power factor range

0–1, inductive, capacitive, or nonlinear, to
2kVA

No load input power (producing output
voltage)

≤25W

Load sense power

≤4W (1s interval) ≤2W (3s interval)

Standby mode power draw
(no output, display off)

≤0.5W

Off mode current draw

≤2mA

Advertising