Electrical specifications: charge mode – Xantrex Technology PROsine 2.0 User Manual

Page 123

Advertising
background image

Electrical Specifications: Charge Mode

445-0089-01-01

A–3

Electrical Specifications: Charge Mode

AC Input

Operating voltage range

90–135Vac

Nominal current

15Aac at 100A charge, 120Vac in

Power factor (100A charge, 120Vac in)

≥0.98 on sine input

Nominal frequency

60Hz

DC Output

Nominal voltage

12.0Vdc

Min battery voltage for charging

0.0Vdc

Max output voltage

17.5Vdc

Nominal output current

100A @

≤15.0Vdc

Equalize mode max current

≥10A @ ≤17.5Vdc

Charger current derating

Automatically reduce charger current as internal
temperature exceeds 80

°

C, input Vac

approaches low transfer, and ac input current
approaches 80% of breaker setting.

Efficiency at nominal output

≥84%

Other

Battery type settings

Gel, Flooded, AGM, Pb-Ca

Battery size settings

50–2000 Ahr

Charge algorithms

Custom 3-stage with factory default set points.
Custom 2-stage as above.
Manually engaged, equalize, with factory
defaults.
CV/CC. User programmable setpoints.

Independent battery banks

1

Advertising