Adjustable From the Configure Battery Menu

NOTE
Settings below are for Battery Type = Generic Gel.

Battery Size

200Ah

**

Default Battery Temperature

Warm

Battery Type

Generic Gel

**

Battery Temp. Coefficient

–27mV/°C

Bulk Mode Settings:

Max Voltage

Max Current (%C)

Threshold Voltage

Threshold Timeout

14.2V

25%

13.8V

3min

Absorption Mode Settings:

Max Voltage

Max Current (%C)

Max Timeout

Threshold Current (%C)

Threshold Timeout

14.2V

25%

8hr

1%

3min

Overcharge Mode Settings:

Max Voltage

Max Current (%C)

Max Timeout

14.2V

20%

0

Float Mode Settings:

Max Voltage

Max Current (%C)

Max Timeout

Threshold Voltage

Threshold Timeout

13.8V

200%

21days

12.5V

15min

Equalize Mode Settings:

Max Voltage

Max Current (%C)

Max Timeout

Threshold Voltage

Threshold Timeout

13.8V

200%

0

0

0

Constant Mode Settings:

Voltage Setpoint

Current Setpoint

13.5V

100A

Charger Mode

Standalone

Charger Type

3-Step

Charger High Battery V
Warning Offset

1.0V

NOTE
The values opposite the gray bar are set when you select a battery type. If you did
not subsequently change these settings, they do not need to be recorded.

Table 1-1 PROsine Default Values

Item

Default Value

Your Settings