Configure prosine—advanced menu – Xantrex Technology PROsine 2.0 User Manual

Page 76

Advertising
background image

Configuration

4–8

445-0089-01-01

Configure PROsine—Advanced Menu

Menu Choices or Information Displayed

Load Sensing

Select Enabled if you want the unit to periodically search for the presence of an
AC load while it is inverting. The unit will “sleep” if the load it detects is less than
the Load Sensing setting.
Select Disabled if you do not want the unit to search for an AC load.
For further information about load sensing, see “Load Sensing Mode” on page 5–
5.

Load Sense Power

This setting determines what power the inverter needs to detect before it will start
automatically (if Load Sensing is Enabled). Settings range between 10 and
255W.

Load Sense Interval

This is the amount of time between checks for the presence of an AC power load.
To save power while the unit is load sensing, increase the interval. The range is
0.5 to 25 seconds.

Menu Display

(if different from Menu Item)

Menu Items

Access

Load Sensing

User

Load Sense Power

User

Load Sense Interval

User

Low AC Transfer (V)

User

Low AC Transfer (Hz)

User

High AC Transfr (V)

High AC Transfer (V)

User

High AC Transfr (Hz)

High AC Transfer (Hz)

User

AC Series Mode

Installer

Inverter Low V Shutdown

User

Inverter Low V Warning

User

INV Low V Restrt Hyst

Inverter Low V Restart Hysteresis

User

Run Without Panel

User

Inverter After Reset (Without Panel)

User

Charger After Reset (Without Panel)

User

Auto Restart After Error

User

Reset to Dflts

Reset to Defaults

Installer