Default Values for the PROsine System

445-0089-01-01

1–9

Default Values for the PROsine System

Table 1-1 lists the default settings for the PROsine system. Record your settings in
the right-hand column after you have configured the PROsine. This information
will be valuable if you need to reconfigure your system or call Xantrex Customer
Service

Table 1-1 PROsine Default Values

Item

Default Value

Your Settings

NOTE
At a minimum, configure the items marked with a

**

after installation.

Adjustable From the Configure PROsine—Basic Menu

AC Breaker Size

15 amps

**

Adjustable From the Configure PROsine—Advanced Menu

Load Sensing

Disabled

Load Sense Power

100 Watts

Load Sense Interval

1 second

Low AC Transfer (V)

90V

Low AC Transfer (Hz)

55Hz

Hi AC Transfer (V)

130V

Hi AC Transfer (Hz)

65Hz

AC Series Mode

Standalone

Inverter Low V Shutdown

10V

Inverter Low V Warning

+0.5V

Iverter Low V Restart
Hysteresis

2.5V

Run Without Panel

NO

Inverter Enabled on Reset
Without Panel

Disabled

Charger Enabled on Reset
Without Panel

Disabled

Auto Restart After Error

NO

**

Adjustable From the Configure Display Panel Menu

Audible Alarm

OFF

LCD Backlight Mode

Auto

LCD Backlight Brightness

50%

LCD Backlight Timeout

20 seconds

Temperature

Farenheit