TROUBLESHOOTING

PROBLEM

CAUSE

SOLUTION

No display on panel.

1. No 115VAC to 1T.

1a. Check wiring and fuse

Unit will not operate.

3FU

b. Check wiring emergency

stop contacts 5 to L of CTB2
Terminal Block.

c. Replace 1T

2. No 24VAC to Microboard

2. Check wiring 1T to

Microboard.

3. 1T defective, no

3. Replace 1T

24VAC output.

4. Short in wire to temp. sensors

4. Unplug connections at

or pressure transducers.

Microboard to isolate.

5. Defective Microboard

5. Replace Microboard.

or Display board.

NOTE: Contact YORK

Service before
Replacing circuit Boards!

“FLOW SWITCH/REM

1. No chilled liquid flow.

1. Check chilled liquid flow.

STOP NO RUN PERMISSIVE”

2. Flow switch improperly

2. Check that the flow switch

installed.

is installed according to

manufacturer’s
instructions.

3. Defective flow switch.

3. Replace flow switch.

4. Remote cycling device open.

4. Check cycling devices

connected to terminals
13 & 14 of the CTB1
Terminal Block.

“LOW SUCTION PRESSURE”

1. Improper suction pressure

1. Adjust per recommended

FAULT

cut-outs adjustments.

settings.

2. Low refrigerant charge.

2. Repair leak if necessary

and add refrigerant.

3. Fouled filter dryer.

3. Change dryer/core.

TABLE 50 – TROUBLESHOOTING

CONT’D