YORK INTERNATIONAL

107

FORM 150.62-NM1

PROBLEM

CAUSE

SOLUTION

“MP / HPCO” FAULT

1. Compressor internal motor

1. Verify refrigerant charge is

protector (MP) open.

not low. Verify superheat
setting of

°

10 - 15

°

F (5.6

°

-

8.3°C). Verify correct com-
pressor rotation. Verify
compressor is not over
loaded.

2. External overload tripped.

2. Determine cause and reset.

3. HPCO switch open

3. See “High Press. Disch.”

Fault

4. Defective HPCO switch

4. Replace HPCO switch

5. Defective CR relay

5. Replace relay

COMPRESSOR(S) WON’T

1. Demand not great enough.

1. No problem. Consult

START

“Installation” Manual to aid
in understanding compres-
sor operation and capacity
control.

2. Defective water temperature

2. Compare the display with a

sensor.

thermometer. Should be
within +/- 2 degrees. Refer
to Service section for RWT/
LWT temp./voltage table.

3. Contactor/Overload failure

3. Replace defective part.

4. Compressor failure

4. Diagnose cause of failure

and replace.

LACK OF COOLING EFFECT

1. Fouled evaporator surface.

1. Contact the local YORK

Low suction pressure will

service representative.

be observed.

2. Improper flow through the

2. Reduce flow to within chiller

evaporator.

design specs. See Limita-
tions in Installation section.

3. Low refrigerant charge.

3. Check subcooling and add

Low suction pressure will

charge as needed.

be observed.