Service and Troubleshooting

*

The operational and fault codes sent to pages 56 through 59 are defined in Table 54. Note that this table of fault and op codes is for all
DX products. The codes that are grayed out are not used on this unit.

TABLE 53 – ISN TRANSMITTED DATA

ISN PAGE

TYPE

DATA

P42

DIGITAL

SYS 1 LIQUID LINE SOLENOID

VALVE

P43

DIGITAL

SYS HOT GAS BYPASS VALVE

P44

DIGITAL

P45

DIGITAL

P46

DIGITAL

SYS 2 LIQUID LINE SOLENOID

VALVE

P47

DIGITAL

LEAD SYSTEM (0=SYS 1, 1 SYS 2)

P48

DIGITAL

P49

DIGITAL

P50

DIGITAL

CHILLED LIQUID TYPE

(0=WATER, 1=GLYCOL)

P51

DIGITAL

AMBIENT CONTROL MODE

(0=STD, 1 = AMB)

P52

DIGITAL

LOCAL / REMOTE CONTROL

MODE (0=LOCAL, 1=REMOTE)

P53

DIGITAL

UNITS (0=IMPERIAL, 1=SI)

P54

DIGITAL

LEAD/LAG CONTROL MODE

(0=MANUAL, 1=AUTO)

P55

DIGITAL

P56

CODED

*SYS 1 OPERATIONAL CODE

P57

CODED

*SYS 1 FAULT CODE

P58

CODED

*SYS 2 OPERATIONAL CODE

P59

CODED

*SYS 2 FAULT CODE

P60

CODED

SYS 1 COMP RUNNING

ISN PAGE

TYPE

DATA

P61

CODED

SYS 1 COND FANS RUNNING

P62

CODED

SYS 2 COMP RUNNING

P63

CODED

SYS 2 COND FANS RUNNING

P64

CODED

P65

ANALOG

UNIT CONTROL MODE

0=LEAVING WATER,

1=RETURN WATER

2=DISCHARGE AIR,

3= SUCTION PRESSURE

P66

ANALOG

ANTI-RECYCLE TIME

(PROGRAMMED)

P67

ANALOG

LEAVING CHILLED LIQUID

TEMP CUTOUT

P68

ANALOG

LOW AMBIENT TEMP CUTOUT

P69

ANALOG

P70

ANALOG

LOW SUCTION PRESS CUTOUT

P71

ANALOG

HIGH DISCHARGE PRESS

CUTOUT

P72

ANALOG

SETPOINT

P73

ANALOG

COOLING RANGE

P74

ANALOG

SETPOINT 2

(SP CONTROL)

P75-P84

NO DATA

ALL ZEROS