Operational limitations (metric), Table 11 – temperatures and flows, Voltage limitations – York YCAL0080SC User Manual

Page 32: Table 12 – voltages

Advertising
background image

YORK INTERNATIONAL

32

OPERATIONAL LIMITATIONS (METRIC)

TABLE 11 – TEMPERATURES AND FLOWS

YCAL00

LEAVING WATER

COOLER FLOW (L/S)

AIR ON CONDENSER (°C)

TEMPERATURE (°C)

MIN

1

MAX

2

MIN

MAX

MIN

4

MAX

5

14SC

4.4

12.8

1.9

3.8

-3.9

51.7

20SC

4.4

12.8

1.9

3.8

-3.9

51.7

24SC

4.4

12.8

2.2

4.4

-3.9

51.7

30SC

4.4

12.8

2.8

4.7

-3.9

51.7

34SC

4.4

12.8

4.7

6.9

-3.9

51.7

40SC

4.4

12.8

4.7

15.8

-3.9

51.7

44SC

4.4

12.8

4.7

15.8

-3.9

51.7

50SC

4.4

12.8

4.7

15.8

-3.9

51.7

60SC

4.4

12.8

4.7

15.8

-3.9

51.7

64SC

4.4

12.8

8.2

24.6

-3.9

51.7

70SC

4.4

12.8

8.2

24.6

-3.9

51.7

74SC

4.4

12.8

8.2

24.6

-3.9

51.7

80SC

4.4

12.8

7.6

27.1

-3.9

51.7

NOTES:

1. Standard units cannot be operated below 4.4°C leaving chilled water temperature.

2. For leaving water temperature higher than 12.8°C, contact the nearest YORK Office for application guidelines.

3. The evaporator is protected against freeze-up to -28.9°C with an electrical heater as standard.

4. Operation below -3.9°C requires Optional Low Ambient Kit for operation to -17.8 °C.

5. Operation above 46.1°C requires Optional High Ambient Kit for operation to 51.7°C.

VOLTAGE LIMITATIONS

The following voltage limitations are absolute and op-
eration beyond these limitations may cause serious
damage to the compressor.

UNIT POWER

MIN.

MAX.

200-3-60

180

220

230-3-60

207

253

380-3-60

355

415

460-3-60

414

506

575-3-60

517

633

TABLE 12 – VOLTAGES

Installation

Excessive flow will cause damage to
the cooler. Do not exceed max. cooler
flow. Special care should be taken
when multiple chillers are fed by a
single pump.

1