Electrical data, Table 1 – micropanel power supply – York YCAL0080SC User Manual

Page 20

Advertising
background image

YORK INTERNATIONAL

20

TABLE 1 – MICROPANEL POWER SUPPLY

OVER CURRENT PROTECTION,

UNIT VOLTAGE

UNIT VOLTAGE

CONTROL POWER

MCA

SEE NOTE B

NF DISC Sw

NOTE A

MIN

MAX

MODELS w/o

CONTROL TRANS

115-1-60/50

15A

10A

15A

30 A / 240V

-17

200-1-60

15A

10A

15A

30 A / 240V

-28

230-1-60

15A

10A

15A

30 A / 240V

MODELS w/

-40

380-1-60

15A

10A

15A

30 A / 480V

CONTROL TRANS

-46

460-1-60

15A

10A

15A

30 A / 480V

-58

575-1-60

15A

10A

15A

30 A / 600V

A. Minimum #14 AWG, 75

°

C, Copper Recommended

B. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker

ELECTRICAL DATA

IT IS POSSIBLE THAT MULTIPLE SOURCES OF POWER CAN BE SUPPLYING
THE UNIT POWER PANEL. TO PREVENT SERIOUS INJURY OR DEATH, THE
TECHNICIAN SHOULD VERIFY THAT NO LETHAL VOLTAGES ARE PRESENT
INSIDE THE PANEL AFTER DISCONNECTING POWER, PRIOR TO WORKING ON
EQUIPMENT.

THE UNIT EVAPORATOR HEATER USES 120 VAC. DISCONNECTING 120 VAC
POWER FROM THE UNIT, AT OR BELOW FREEZING TEMPERATURES, CAN
RESULT IN DAMAGE TO THE EVAPORATOR AND UNIT AS A RESULT OF THE
CHILLED LIQUID FREEZING.