Table 29 – program key limits and defaults – York YCAL0080SC User Manual

Page 79

Advertising
background image

YORK INTERNATIONAL

79

FORM 150.62-NM1

Another anti-recycle timer is started each time the sys-
tems number one compressor cycles off. This anti-re-
cycle time is fixed at 120 seconds and starts to count-
down when the systems number one compressor cycles
off.

The anti-recycle message is displayed when the sys-
tem is unable to start due to either of the anti-recycle
timers being active (counting down). The actual time
displayed will be the longer of the two timers, start-to-
start or stop-to-start.

The Fan Control On Pressure is the programmed pres-
sure value that is used to stage the condenser fans on,
in relation to discharge pressure. Refer to Condenser
Fan Control in the UNIT OPERATION section and
Tables 38, 39, and 40, 41.

The Fan Differential Off Pressure is the programmed
differential pressure value that is used to stage the con-
denser fans off, in relation to discharge pressure. Refer
to Condenser Fan Control in the UNIT OPERATION
section and Tables 38, 39 and 40, 41.

The TOTAL NUMBER OF COMPRESSORS are the
amount of compressors in the chiller, and determines
the stages of cooling available. Notice in Table 29 the
chiller is a single or dual refrigerant circuit.

This must be programmed correctly to
assure proper chiller operation.

T O T A L

N U M B E R

O F

C O M P R E S S O R S

=

6

F A N

C O N T R O L

O N

P R E S S U R E = X X X P S I G

F A N

D I F F E R E N T I A L

O F F

P R E S S U R E = X X X P S I G

TABLE 29 – PROGRAM KEY LIMITS AND DEFAULTS

PROGRAM VALUE

MODEL

LOW LIMIT

HIGH LIMIT

DEFAULT

DISCHARGE PRESSURE CUTOUT

200 PSIG

399 PSIG

395 PSIG

13.8 BARS

27.5 BARS

27.2 BARS

SUCTION PRESSURE CUTOUT

WATER COOLING

44.0 PSIG

70.0 PSIG

44.0 PSIG

3.03 BARS

4.83 BARS

3.03 BARS

GLYCOL COOLING

20.0 PSIG

70.0 PSIG

44.0 PSIG

1.38 BARS

4.83 BARS

3.03 BAR

LOW AMBIENT TEMP. CUTOUT

STANDARD AMBIENT

25.0°F

60.0°F

25.0°F

-3.9°C

15.6°C

-3.9°C

LOW AMBIENT

0°F

60.0°F

25.0°F

-17.8°C

15.6°C

-3.9°C

LEAVING CHILLED LIQUID

WATER COOLING

36°F

2.2°C

TEMP. CUTOUT

GLYCOL COOLING

8.0°F

36.0°F

36.0°F

-13.3°C

2.2°C

2.2°C

ANTI-RECYCLE TIMER

300 SEC.

600 SEC.

600 SEC.

FAN CONTROL ON-PRESSURE

225 PSIG

300 PSIG

230 PSIG

15.5 BARS

20.7 BARS

15.9 BARS

FAN DIFFERENTIAL OFF-PRESSURE

50 PSIG

150 PSIG

80 PSIG

3.45 BARS

10.3 BARS

5.52 BARS

TOTAL NUMBER OF COMPRESSORS

SINGLE SYSTEM

2

3

3

TWO SYSTEMS

4

6

6

2