Fig. 4 – optional single point power wiring, Control panel, Power panel – York YCAL0080SC User Manual

Page 16

Advertising
background image

YORK INTERNATIONAL

16

Control Panel

See electrical note 9

Power Panel

Micropanel

Field Unit Power
Supply

1L1

1L2

1L3

N-F Disconnect
Sw. OR Molded
Case Circuit
Bkr.

Field 120-1-60 Micropanel
Power Supply if control
transformer not supplied

GRD

CTB2

2

L

13

14

CTB1

Flow Switch

Electrical Notes and Legend located on Page 18 and 19.

FIG. 4 – OPTIONAL SINGLE POINT POWER WIRING

OPTIONAL SINGLE-POINT POWER SUPPLY WIRING

N-F DISC SW OR CIRC BKR (0014 - 0080)

LD04485

IT IS POSSIBLE THAT MULTIPLE SOURCES OF POWER CAN BE SUPPLYING
THE UNIT POWER PANEL. TO PREVENT SERIOUS INJURY OR DEATH, THE
TECHNICIAN SHOULD VERIFY THAT NO LETHAL VOLTAGES ARE PRESENT
INSIDE THE PANEL AFTER DISCONNECTING POWER, PRIOR TO WORKING ON
EQUIPMENT.

THE UNIT EVAPORATOR HEATER USES 120 VAC. DISCONNECTING 120 VAC
POWER FROM THE UNIT, AT OR BELOW FREEZING TEMPERATURES, CAN
RESULT IN DAMAGE TO THE EVAPORATOR AND UNIT AS A RESULT OF THE
CHILLED LIQUID FREEZING.