Fig. 6 – leaving water temperature control, Unit controls – York YCAL0080SC User Manual

Page 86

Advertising
background image

YORK INTERNATIONAL

86

FIG. 6 – LEAVING WATER TEMPERATURE CONTROL

TABLE 32 – LEAVING CHILLED LIQUID CONTROL FOR 6 COMPRESSORS (8 STEPS)

TABLE 33 – LEAVING CHILLED LIQUID CONTROL FOR 4 COMPRESSORS (6 STEPS)

20 sec.

30 sec.

60 sec.

control range

60 sec.

unloading

unloading

unloading

(no compressor staging)

loading

42.5°F

43.5°F

44.0°F

46.0°F

48.0°

(5.8°C)

(6.4°C)

(6.7°C)

(7.8°C)

(8.9°C)

Low Limit

Setpoint

High limit

Leaving Water Temp. Control – Compressor Staging

Setpoint = 46.0°F (7.8°C) Range = +/- 2°F(1.1°C)

LWT

LEAD SYSTEM

LAG SYSTEM

*STEP

COMP 1

COMP 2

COMP 3

COMP 1

COMP 2

COMP 3

0

OFF

OFF

OFF

OFF

OFF

OFF

1

ON+HG

OFF

OFF

SEE NOTE 1

OFF

OFF

OFF

2

ON

OFF

OFF

OFF

OFF

OFF

3

ON

OFF

OFF

SEE NOTE 2

ON

OFF

OFF

4

ON

ON

OFF

SEE NOTE 3

OFF

OFF

OFF

5

ON

ON

OFF

ON

OFF

OFF

6

ON

ON

OFF

ON

ON

OFF

7

ON

ON

ON

ON

ON

OFF

8

ON

ON

ON

ON

ON

ON

LEAD SYSTEM

LAG SYSTEM

*STEP

COMP 1

COMP 2

COMP 1

COMP 2

0

OFF

OFF

OFF

OFF

1

ON+HG

OFF

SEE NOTE 1

OFF

OFF

2

ON

OFF

OFF

OFF

3

ON

OFF

SEE NOTE 2

ON

OFF

4

ON

ON

SEE NOTE 3

OFF

OFF

5

ON

ON

ON

OFF

6

ON

ON

ON

ON

* STEP can be viewed using the OPER DATA key and scrolling to COOLING DEMAND.

Unit Controls

Advertising