Isn control, Received data (control data), Table 51 – isn received data – York YCAL0080SC User Manual

Page 109: Transmitted data, Table 52 – isn transmitted data

Advertising
background image

YORK INTERNATIONAL

109

FORM 150.62-NM1

RECEIVED DATA (CONTROL DATA)

The Middle Market receives 8 data values from the ISN.
The first 4 are analog values and the last 4 are digital
values. These 8 data values are used as control pa-
rameters when in REMOTE mode. When the unit is in
LOCAL mode, these 8 values are ignored. If the unit
receives no valid ISN transmission for 5 minutes it will
revert back to all local control values. Table 51 lists the
5 control parameters. These values are found under
feature 54 on the ISN.

TRANSMITTED DATA

After receiving a valid transmission from the ISN, the
unit will transmit either operational data or history buffer
data depending on the “History Buffer Request” in page
10. Data must be transmitted for every ISN page under
feature 54. If there is no value to be sent to a particular
page, a zero will be sent. Tables 52 - 53 show the data
values and page listings for this unit.

ISN CONTROL

TABLE 51 – ISN RECEIVED DATA

TABLE 52 – ISN TRANSMITTED DATA

ISN PAGE

CONTROL DATA

P03

SETPOINT

P04

LOAD LIMIT STAGE (0,1, 2)

P05

COOLING RANGE (DAT MODE ONLY)

P06

P07

START/STOP COMMAND

P08

P09

P10

HISTORY BUFFER REQUEST

ISN PAGE

TYPE

DATA

P11

ANALOG LEAVING CHILLED LIQUID TEMP.

P12

ANALOG RETURN CHILLED LIQUID TEMP.

P13

ANALOG MIXED CHILLED LIQUID TEMP.

P14

ANALOG DISCHARGE AIR TEMP.

P15

ANALOG —

P16

ANALOG AMBIENT AIR TEMP.

P17

ANALOG —

P18

ANALOG SYS 1 RUN TIME (SECONDS)

P20

ANALOG SYS 1 DISCHARGE PRESSURE

P21

ANALOG —

P22

ANALOG —

P23

ANALOG —

P24

ANALOG SYS 1 ANTI-RECYCLE TIMER

P25

ANALOG ANTI-COINCIDENT TIMER

P27

ANALOG SYS 2 RUN TIME (SECONDS)

P28

ANALOG SYS 2 SUCTION PRESSURE

P29

ANALOG SYS 2 DISCHARGE PRESSURE

P33

ANALOG SYS 2 ANTI-RECYCLE TIMER

P35

ANALOG NUMBER OF COMPRESSORS

P36

DIGITAL

SYS 1 ALARM

P37

DIGITAL

SYS 2 ALARM

P38

DIGITAL

EVAPORATOR HEATER STATUS

P39

DIGITAL

EVAPORATOR PUMP STATUS

P40

DIGITAL

P41

DIGITAL

3

Advertising
This manual is related to the following products: