Table 44 – microboard binary inputs, Table 45 – microboard analog inputs, Table 46 – microboard outputs – York YCAL0080SC User Manual

Page 97

Advertising
background image

YORK INTERNATIONAL

97

FORM 150.62-NM1

*

The 30 dc unregulated supply is not an input. This voltage originates on the microboard and is used to supply the contacts for the binary
inputs.

TABLE 46 – MICROBOARD OUTPUTS

TB3-2

SYSTEM 1 COMPRESSOR 1

TB3-3

SYS 1 LIQUID LINE SOLENOID VALVE

TB3-4

SYSTEM 1 COMPRESSOR 2

TB3-5

SYSTEM 1 COMPRESSOR 3

TB3-6

SYSTEM 1 HOT GAS BYPASS VALVE

TB3-8

SYSTEM 2 COMPRESSOR 1

TB3-9

SYS 2 LIQUID LINE SOLENOID VALVE

TB3-10 SYSTEM 2 COMPRESSOR 2

TB4-1

SYSTEM 2 COMPRESSOR 3

TB4-2

SYS 1 CONDENSER FAN STAGE 1

TB4-4

SYS 1 CONDENSER FAN STAGE 2

TB4-5

SYS 1 CONDENSER FAN STAGE 3

TB4-6

SYS 2 CONDENSER FAN STAGE 1

TB4-8

SYS 2 CONDENSER FAN STAGE 2

TB4-9

SYS 2 CONDENSER FAN STAGE 3

TB4-10 EVAPORATOR HEATER

TB5-1

SYSTEM 1 ALARM

TB5-2

SYSTEM 2 ALARM

TB5-3

EVAPORATOR PUMP STARTER

TABLE 44 – MICROBOARD BINARY INPUTS

*J9-1 30VDC UNREGULATED SUPPLY

J9-2

UNIT ON/OFF SWITCH

J9-3

PWM TEMP RESET

OR LOAD LIMIT STAGE 2 ON 3 & 6 COMP UNITS

J9-4

LOAD LIMIT STAGE 1

J9-5

FLOW SWITCH AND REMOTE START / STOP

(SYS 1 ZONE THERMOSTAT - YCUL ONLY)

J9-6

SYSTEM 2 ZONE THERMOSTAT - YCUL ONLY

J9-7

SINGLE SYSTEM SELECT

(JUMPER = SINGLE SYS, NO JUMPER=TWO

SYS)

J9-8

CR1 (SYS 1 MOTOR PROTECTOR / HIGH

PRESS CUTOUT)

J9-9

CR2 (SYS 2 MOTOR PROTECTOR / HIGH

PRESS CUTOUT)

TABLE 45 – MICROBOARD ANALOG INPUTS

J4-10 Sys 1 Suction Press Transducer or

Sys 1 Low Press Switch

J4-11 SPARE

J4-12 Sys 1 Discharge Pressure Transducer (optional)

J5-12 Sys 1 Suction Temp Sensor - YCUL Option

J5-13 Sys 2 Suction Temp Sensor - YCUL Option

J5-14 SPARE

J5-15 SPARE

J6-7

Ambient Air Temperature Sensor

J6-8

Leaving Chilled Liquid Temperature Sensor

J6-9

Return Chilled Liquid Temperature Sensor

or

Discharge Air Temp Sensor - YCUL Only

J7-10

Sys 2 Suct Press Transducer

or

Sys 2 Low Press Switch

J7-11 SPARE

J7-12 Sys 2 Discharge Pressure Transducer (optional)

J8-5

Sys 1 Ground Fault Circuit

J8-6

Sys 2 Ground Fault Circuit