Display/print keys, Oper data key, Unit controls – York YCAL0080SC User Manual

Page 66

Advertising
background image

YORK INTERNATIONAL

66

The Display/Print keys allow the user to retrieve sys-
tem and unit information that is useful for monitoring
chiller operation, diagnosing potential problems, trouble-
shooting, and commissioning the chiller.

System and unit information, unit options, setpoints, and
scheduling can also be printed out with the use of a
printer. Both real-time and history information are avail-
able.

OPER DATA Key

The OPER DATA key gives the user access to unit and
system operating parameters. When the OPER DATA
key is pressed, system parameters will be displayed
and remain on the display until another key is pressed.
After pressing the OPER DATA key, the various operat-
ing data screens can be scrolled through by using the
UP and DOWN arrow keys located under the “ENTRY”
section.

DISPLAY/PRINT KEYS

With the “UNIT TYPE” programmed as a liquid chiller
(under the Options key), the following is a list of operat-
ing data screens in the order that they are displayed:

This display shows chilled leaving and return liquid tem-
peratures. The minimum limit on the display for these
parameters are 9.2°F (-12.7°C). The maximum limit
on the display is 85.4°F (29.7°C).

This display shows the ambient air temperature. The
minimum limit on the display is 0.4°F (-17.6°C).The
maximum limit on the display is 131.2°F (55.1°C).

L C H L T

=

4 6 . 2 ° F

R C H L T

=

5 7 . 4 ° F

°

A M B I E N T

A I R

T E M P

=

8 7 . 5 ° F

00067VIP

Unit Controls

Advertising
This manual is related to the following products: